10 Zone Master Call Controller
10 Zone Master Call Controller c/w 300mA PSU (Flush Version)
- Compatible with C-TEC’s entire range of 800 Series field devices.
- Housed in an attractive flush mounting plastic enclosure measuring just 214mm x 178mm.
- Two call levels - standard (constant tone) and emergency (intermittent tone).
- Optional mute and call accept/reset buttons.
- ‘Call Accept’ functionality allows staff to send an intermittent call acknowledgment signal to calling zones to confirm help is on the way (dependent on wiring and field devices used).
- Includes a 12V 300mA PSU and 2 volt-free relay contacts which activate on a standard or emergency call.
- Innovative slide-in labelling system.
- Zones can be wired in 4 or 6 core (7/02) stranded security cable.
- Additional master controllers and expansion units available for use as repeaters on larger sites.
- Optional boxed PSUs c/w with space for a 12V VRLA battery available for sites where a standby battery facility is required.
Mains supply | 230V 50/60Hz. (36mA max. current). |
Internal power supply | 11V d.c. (300mA max. current when powered by Mains). |
Quiescent current | 0mA (none). |
Alarm current | Determined by the number/type of field devices connected to the call controller/system. |
Auxiliary relays | 2 volt free relay contacts (NO/C/NC). Activate when a standard or emergency call is received by the controller. Both relays rated at 30V d.c. @ 1A. |
Auxiliary inputs | External PSU Input: 9V-15V d.c. @ 400mA (suitable for use with an NC951B 12V 1A boxed PSU which has space available for a 12V 7AH battery). |
Indicators | Green Power on LED; 10 x red Zonal Alarm LEDs (lit steady for a Standard call, pulse for an Emergency call); Internal buzzer (on steady for any Standard call, intermittent for any Emergency call). |
Controls | 2 Buttons - (A) Reset or inactive ; (B) 'Mute' or 'Call Accept'. (Both buttons are link selectable). If Call Accept is selected indicators on relevant field devices will emit a slow intermittent tone to reassure users help is on the way. |
Expansion connections | CONN2 allows the connection of 1 x NC910EF 10 Zone Expansion Unit or 1x NC920EF 20 Zone Expansion Unit. |
Call acknowledgement functionality | Yes. |
Product dimensions (mm) | 214 W x 178 H x 70 D mm (overall). Hole required for flush mounting is 176 W x 162 H x 55 D mm. |
Construction & finish | Plastic detachable lid and back box. RAL7035. |
IP Rating | IP41. |
Weight | 1.47kg. |
Operating conditions/temperature | -5ºC to +40ºC. Max. relative humidity 95% non-condensing. |